Description
TECHNICAL SPECIFICATIONS
Mixed Fixed Type
Rated Voltage | AC 208 V, AC 400 V, AC 690 V |
---|---|
Electrical Specification | |
Input Voltage Range |
AC 208 V: AC 166~250 V AC 400 V: AC 308~456 V AC 690 V: AC 384~880 V |
Electric Connection |
AC 208 V & 400 V: 3P4W, 3P3W AC 690 V: 3P3W |
Rated Current per Module |
AC 208 V: 50 A, 75 A, 100 A, 150 A AC 400 V: 30 A, 50 A, 75 A, 100 A, 150 A AC 690 V: 100 A |
Rated Current per Cabinet |
AC 208 V: 50~750 A (Module combination) AC 400 V: 30~750 A (Module combination) AC 690 V: 100~500 A (Module combination) |
Rated Frequency | 50(60) Hz ± 10% |
Input Voltage THD Range | ≤ 15% |
Redundancy | Each module is an independent filtering system |
Harmonic Elimination Range | 2nd~50th order (Selectable) |
Harmonic Filtering Degree | 0~100% programmable per harmonic in Ampere value |
Harmonic Filtering Performance |
Filter up to 98% harmonics at rated load THDv < 3%, THDi < 5% after filtering |
Reactive Power Compensation Capability | Both inductive and capacitive reactive power |
Reactive Power Compensation Performance | Cosφ ≥ 0.99 after compensation (if the APF capacity is sufficient) |
Imbalance Correction Capability | Mitigate negative and zero sequence |
Full Response Time | < 10 ms |
Instant Response Time | < 100 us |
Thermal Loss |
AC 208 V: ≤ 5% of APF rated capacity AC 400/690 V: ≤ 3% of APF rated capacity |
Output Current Limitation | Automatic (100% rated capacity) |
Parallel Expansion (System) | Up to 10 Racks (7 modules per cabinet) |
MTBF | > 100,000 hours |
Reviews
There are no reviews yet.